Except as provided in subsection (c), cross-connection control devices must be inspected at least annually by a person approved by the Agency or its designee as a cross-connection control device inspector (CCCDI). The inspection of mechanical devices must include physical testing in accordance with the manufacturer's instructions.
A) make, model, and serial number of the backflow preventer, and its location at the site;
B) date of each test;
C) name and approval number of the person performing the test;
D) type of test kit used and date of its most recent calibration;
E) test results and a brief statement indicating whether the results pass or fail the test;
F) repairs or servicing required;
G) repairs and date completed; and
H) servicing performed and date completed.
1) Each applicant for CCCDI Approval must:
2) CCCDIs must renew the CCCDI Approval each year between May 1 and June 30. An application for CCCDI renewal will be sent by the Agency or its designee, and must be completed and returned by June 30 of the renewal year. CCCDIs must complete an eight-hour recertification course every three years from the date of the original issuance of the CCCDI license. The course must be offered by the Environmental Resources Training Center or the Agency's delegate and include a written and practical exam demonstrating competency in backflow prevention testing.
3) A CCCDI Approval or admission to an examination for CCCDI Approval must be suspended, revoked, or not issued by the Agency for any one or more of the following causes: